Air circuit breakers
AW45 Air Circuit Breakers
Compare 2000–6300 A frames for low-voltage switchboards. Select rated current, 3 or 4 poles, fixed or withdrawable construction, and the required controller and releases.
At a glance
Specifications & model comparison
- Rated current
- 630–6300 A across listed frames
- Rated voltage
- 400 / 690 V AC
- Poles
- 3P / 4P
- Frequency
- 50/60 Hz
- Mounting
- Fixed / withdrawable
- Ambient temperature
- −5 to +40 °C; 24 h average ≤35 °C
| Frame | Rated currents (A) | Icu 400 / 690 V (kA) | Ics = Icw 400 / 690 V (kA) | Enquiry |
|---|---|---|---|---|
| AW45-2000 | 630, 800, 1000, 1250, 1600, 2000 | 80 / 50 | 50 / 40 | Select for RFQ → |
| AW45-3200 | 2000, 2500, 3200 | 100 / 65 | 80 / 50 | Select for RFQ → |
| AW45-4000 | 2000, 2500, 3200, 4000 | 100 / 65 | 80 / 50 | Select for RFQ → |
| AW45-6300 | 4000, 5000, 6300 | 120 / 80 | 100 / 65 | Select for RFQ → |
Include the required pole count, electrical configuration and accessories in your enquiry. Configuration descriptions do not replace the complete ordering code.
Mechanical reference
Outline & mounting dimensions
Before ordering
Specify the configuration
- Specify the frame and rated current separately. Choose 3P or 4P and the neutral rating (50% In or 100% In) for the selected configuration.
- Select fixed or withdrawable construction and match the panel cut-out, busbar arrangement and mounting drawing.
- Specify the standard M controller or H communication controller, and required long-delay, short-delay, instantaneous and earth-fault protection settings.
- For shunt release, undervoltage release and closing electromagnet, state the required supply: AC 220 V, AC 380 V, DC 110 V or DC 220 V.
- Undervoltage release options include instantaneous and delayed operation (1, 3 or 5 s). Confirm auxiliary contact arrangement and energy-storage motor configuration.
- Installation altitude ≤2000 m; pollution degree III; install within 5° of vertical.
Selection questions
Practical answers for purchasing
Does the frame current identify the complete AW45 breaker?
No. Rated current, pole count, neutral rating, mounting type, controller, release supply and accessories also form part of the ordering configuration.
Are the 400 V and 690 V short-circuit ratings the same?
No. The comparison table lists separate values for each operating voltage.