Application fit
- Compact junction boxes
- Luminaire wiring assemblies
- Equipment harness servicing
CMK-612 to CMK-615 are compact, transparent connectors with blue operating levers and two to five conductor entries. They serve common-potential splices where conductor cross-sections are no greater than 2.5 mm².

| Parameter | Specification |
|---|---|
| Rated voltage | 450 V AC |
| Rated current | 32 A |
| Rigid conductor range | 0.75–2.5 mm² |
| Flexible conductor range | 1.0–2.5 mm² |
| Strip length | 13 mm |
| Operating temperature | −40 to +105 °C |
| Housing material | Transparent polycarbonate (PC) |
| Conductive parts | Tin-plated copper |
| Contact spring | AISI 301 stainless steel |
| Connection arrangement | Common-potential splice |
| Lever material | POM (polyacetal) |
Ratings apply to the listed connector configuration. The permissible circuit current also depends on conductor size, installation conditions and circuit protection. Use copper conductors.
Each model below has its own conductor-entry count. Electrical ratings are not multiplied by the number of entries.
| Model | Conductor entries | Inner pack (pcs) | Carton (pcs) |
|---|---|---|---|
| CMK-612 | 2 | 100 | 6000 |
| CMK-613 | 3 | 100 | 4000 |
| CMK-614 | 4 | 100 | 4000 |
| CMK-615 | 5 | 100 | 4000 |
4 models
Pack quantities describe standard packaging, not minimum order quantities. State the required quantity for each model in your inquiry.
| Model | Depth (mm) | Width (mm) | Height (mm) |
|---|---|---|---|
| CMK-612 | 21.2 | 13 | 9.5 |
| CMK-613 | 21.2 | 18.2 | 9.5 |
| CMK-614 | 21.2 | 23.5 | 9.5 |
| CMK-615 | 21.2 | 29 | 9.5 |

Select CMK-61 for conductors within its 2.5 mm² upper limit. Its 13 mm stripping requirement differs from the 11 mm used by CMK-63 and CMK-41.
CMK-61 accepts rigid wire from 0.75–2.5 mm² and flexible wire from 1.0–2.5 mm², with a 13 mm strip length. CMK-63 accepts larger rigid wire and uses an 11 mm strip length.
The lever opens the spring clamp so that a conductor can be removed and reinserted. Inspect the connector and the conductor before reuse.
Include CMK-61 Blue Lever Connectors model code, quantities, conductor sizes, destination and packaging requirements.