Wenzhou Changsong Electric Co., Ltd.
Catalogs & technical filesContact & inquiryWhatsApp
CHSOINDUSTRIAL ELECTRICALRequest a quote 0→
Copper connectors

AUS-TUBE Copper Compression Sleeves

Tinned copper sleeves for straight copper conductor joints in the AUS dimensional range. Select the sleeve bore and length for the conductor and intended crimp system.

6–1000 mm²T2 copperCompression connection
AUS-TUBE Copper Compression Sleeves
AUS-TUBE · Copper connectors
Technical data

Material, connection & construction

AUS-TUBE product specifications
ParameterSpecification
SeriesAUS-TUBE
Product formCopper Compression Sleeves
Conductor / interfaceCopper-to-copper conductor joint
Body materialT2 copper
Size range6–1000 mm²
Connection methodCompression joint
InsulationNon-insulated; provide application-specific joint insulation and enclosure protection
DimensionsMillimetres; conductor cross-section in mm²
FinishTin-plated copper
Copper purity≥99.9% T2 copper
Lug / sleeve material temperature range−55°C to +150°C; the cable insulation and complete connection may impose a lower limit
Model selection

Models & dimensions

All dimensional values are in millimetres. Conductor sizes are in mm². Use the symbols in the drawing for the selected construction.

Specify AUS-TUBE when ordering connecting sleeves to distinguish them from AUS ring lugs.

AUS-TUBE Copper Compression Sleeves construction
Product construction
AUS-TUBE Copper Compression Sleeves dimension symbols
Dimensional geometry · All dimensions in mm
Use the dimension symbols in this series drawing; symbols can differ between constructions.

AUS-TUBE model dimensions
ModelTube OD DTube ID dOverall length L
AUS-TUBE-65.53.830
AUS-TUBE-1064.530
AUS-TUBE-168.55.550
AUS-TUBE-2510750
AUS-TUBE-3512.58.250
AUS-TUBE-5014.51056
AUS-TUBE-7016.511.556
AUS-TUBE-951913.570
AUS-TUBE-1202115.570
AUS-TUBE-15023.51780
AUS-TUBE-18523.51985
AUS-TUBE-2402921.590
AUS-TUBE-3003224.5100
AUS-TUBE-40038.527.5150
AUS-TUBE-5004231160
AUS-TUBE-6304434.5160
AUS-TUBE-8005240200
1000 mm² large-size sleeve
ModelTube OD DOverall length L
AUS-TUBE-100058200
Application & installation

Select the complete connection

Application fit

  • Straight cable joints and copper-wire splices in protected installations
  • Panel maintenance and planned cable extensions
  • Equipment wiring where the compression joint is insulated and mechanically supported

Ordering checklist

Specify AUS-TUBE construction, conductor material and nominal section, conductor strand class, both conductor sizes, joint space, tool/die system, quantity and required finish.

Installation sequence

  1. Isolate the circuit and verify that it is de-energised. Identify the conductor material, section and strand construction.
  2. Select the matching connector, tool and die combination. Strip to the required insertion length without cutting or losing strands.
  3. Insert the conductor fully and crimp in the sequence and number of compressions specified for the connector/tool system. Do not substitute a die solely because its size marking looks similar.
  4. Inspect the compression, conductor retention and contact alignment. Restore suitable insulation and protection, then carry out the assembly checks before energising.
Practical answers

Frequently asked questions

What distinguishes AUS-TUBE from other cable connectors?

Tinned copper sleeves for straight copper conductor joints in the AUS dimensional range. Select the sleeve bore and length for the conductor and intended crimp system.

How do I select the correct AUS-TUBE size?

Specify AUS-TUBE construction, conductor material and nominal section, conductor strand class, both conductor sizes, joint space, tool/die system, quantity and required finish.

What should I check before ordering this series?

Specify AUS-TUBE when ordering connecting sleeves to distinguish them from AUS ring lugs.

Does the conductor size determine a universal current rating?

No. Connection current depends on the cable material and size, insulation temperature, terminal interface, installation conditions and verified crimp system. Select the whole circuit and connection together.

Can I use any crimping die with the same size number?

No. Die profile, tool force, connector wall thickness and conductor construction work as a system. Use the specified tool/die combination for the chosen connector.

Does this connector provide electrical insulation?

No. These are conductive connection components. Provide the joint insulation, sealing and mechanical protection required by the cable system and installation.

Distributor & panel-builder inquiries

Specify the conductor.
Match the connection.

Include AUS-TUBE model and construction, conductor material and size, stud-hole or joint requirements, quantities and packaging needs.

Request pricing ↗
WhatsApp