UKK Distribution Blocks

UKK160A Power Distribution Block

UKK160A single-pole power distribution block: 160 A, 10–70 mm² main input and 6 branch outputs under a transparent cover.

160 A6 outputsSingle pole
UKK160A Power Distribution Block
UKK160A · UKK Distribution Blocks
Technical data

Product specifications

UKK160A technical specifications
ParameterSpecification
Product modelUKK160A
Rated current160 A
Rated insulation voltage (Ui)1000 V
Electrical arrangementOne common potential / single pole
Main connection10–70 mm² copper conductor
Branch outputs6
Conductor materialNickel-plated copper
Insulating housingFlame-retardant PVC
CoverTransparent polycarbonate
MountingDIN rail or screw fixing
Overall dimensions H × D × W77 × 46 × 29 mm
Mounting centres64 mm
Connections & dimensions

Conductor entries & tightening torque

UKK160A selection table
ConnectionEntriesConductor / busbar sizeTorque (N·m)
Main input110–70 mm²8.5
Auxiliary / jumper entry16–16 mm²3.5
Branch outputs62.5–16 mm²3.5

Connection torque varies with entry size. Ui is an insulation parameter; select the complete installation for its operating voltage and protection requirements.

Additional product reference image
UKK160A original product reference
Application & installation

Select for the complete panel

Choose UKK160A when the feeder is 10–70 mm² and 6 branch connections are required. Keep the sum of branch currents within the block rating and coordinate each branch with conductor size and protective devices.

Application fit

  • Feeder branching in low-voltage distribution panels
  • Power distribution within machinery control cabinets
  • Organised replacement of multiple wires sharing one feeder terminal

Installation sequence

  1. Isolate the circuit and verify that it is de-energised.
  2. Secure the terminal assembly to the matching rail or mounting surface. Keep accessible metal parts separated from other potentials.
  3. Prepare conductors for full engagement in the clamp, without damaged strands or exposed copper outside the entry.
  4. Tighten each entry to the torque listed for that entry size.
  5. Check conductor retention, circuit identification and continuity. Close any fitted cover before energising the completed assembly.
Practical answers

Frequently asked questions

What does UKK160A connect?

UKK160A single-pole power distribution block: 160 A, 10–70 mm² main input and 6 branch outputs under a transparent cover.

Are the outputs separate poles?

No. All entries in a single UKK block share one electrical potential. Use separate blocks for separate phases or neutral.

Is Ui the operating-voltage rating?

No. Rated insulation voltage describes insulation coordination. It is not permission to operate a complete assembly at that voltage.

Does the cover make the block waterproof?

No. Install the block inside an enclosure suited to the operating environment. Keep the cover closed after connection.

What is the additional 6–16 mm² entry for?

It provides an auxiliary connection or a jumper connection to the same potential. The six branch-output entries are listed separately in the connection table.