Application fit
- Feeder branching in low-voltage distribution panels
- Power distribution within machinery control cabinets
- Organised replacement of multiple wires sharing one feeder terminal
UKK250A single-pole power distribution block: 250 A, 35–120 mm² main input and 11 branch outputs under a transparent cover.

| Parameter | Specification |
|---|---|
| Product model | UKK250A |
| Rated current | 250 A |
| Rated insulation voltage (Ui) | 1000 V |
| Electrical arrangement | One common potential / single pole |
| Main connection | 35–120 mm² copper conductor |
| Branch outputs | 11 |
| Conductor material | Nickel-plated copper |
| Insulating housing | Flame-retardant PVC |
| Cover | Transparent polycarbonate |
| Mounting | DIN rail or screw fixing |
| Overall dimensions H × D × W | 96 × 50 × 49 mm |
| Mounting centres | 85 × 29 mm |
| Connection | Entries | Conductor / busbar size | Torque (N·m) |
|---|---|---|---|
| Main input | 1 | 35–120 mm² | 19 |
| Branch outputs | 2 | 6–35 mm² bare / 6–25 mm² with ferrule | 4.4 |
| Branch outputs | 5 | 2.5–16 mm² | 2.7 |
| Branch outputs | 4 | 2.5–10 mm² | 2.7 |
Connection torque varies with entry size. Ui is an insulation parameter; select the complete installation for its operating voltage and protection requirements.

Dimensions in millimetres. Compare the drawing with the option table when selecting a length or connection-position count.

Choose UKK250A when the feeder is 35–120 mm² and 11 branch connections are required. Keep the sum of branch currents within the block rating and coordinate each branch with conductor size and protective devices.
UKK250A single-pole power distribution block: 250 A, 35–120 mm² main input and 11 branch outputs under a transparent cover.
No. All entries in a single UKK block share one electrical potential. Use separate blocks for separate phases or neutral.
No. Rated insulation voltage describes insulation coordination. It is not permission to operate a complete assembly at that voltage.
No. Install the block inside an enclosure suited to the operating environment. Keep the cover closed after connection.
Include UKK250A Power Distribution Block model code, quantities, conductor sizes, destination and packaging requirements.