CHSO / ENCLOSURE CLIMATE CONTROL
KTO 013 & KTS 013 Thermostats
NC heating and NO cooling thermostats in the 013 format. Match the exact housing, dial scale and contact load when replacing an existing unit.
ORDERING CONFIGURATION
Choose contact action and dial range.
| Model | Contact action | Typical circuit |
|---|---|---|
| KTO 013 | NC: opens on temperature rise | Enclosure heater |
| KTS 013 | NO: closes on temperature rise | Filter fan or overtemperature signal |
TECHNICAL DATA
Electrical and mechanical characteristics
| Parameter | Specification |
|---|---|
| Sensor | Thermostatic bimetal |
| Contact system | Snap-action contacts |
| Control action | KTO: NC, opens as temperature rises. KTS: NO, closes as temperature rises. |
| Dial setting range | 0–60 °C standard selection; specify alternatives separately |
| Switching differential | 7 K ±4 K; verify with the selected configuration |
| Mounting | Clip for 35 mm DIN rail |
| Protection type | IP20; install inside a protective enclosure |
| Operating / storage temperature | −45 to +80 °C |
| Humidity | Maximum 90% RH, non-condensing |
| Case dimensions | 60 × 33 × 43 mm reference; confirm case before panel layout |
| Switching load | Specify AC/DC voltage, resistive or inductive load, running current and inrush current |
| Indicator supply | No separate supply required for the mechanical sensing element |
| Alternative dial scales | −20 to +40 °C; −10 to +50 °C; 20 to 80 °C — specify with the enquiry |
DIMENSIONS & CONNECTIONS
Check the selected housing.
The illustrated housing is 60 × 33 × 43 mm. Confirm this case version with the model; a taller 75 mm version appears in earlier specification records.
Application and installation
- Choose by contact action, then verify the switching rating at the actual voltage and load type. An AC resistive rating is not an equivalent DC or motor-load rating.
- Place the thermostat where it senses representative enclosure air. Avoid direct heater discharge, fan jets and local hot spots.
- The switching differential is the temperature gap between opening and closing; it is not a ±7 °C measurement accuracy.
- Confirm terminal numbering, permitted conductor size and tightening torque from the selected unit before wiring.
- Case dimensions differ across versions sold under this suffix. Confirm the sample drawing before treating another thermostat as a drop-in replacement.
SELECTION SUPPORT
Questions before ordering
How should I specify KTO 013 & KTS 013?
Provide the exact model, NC/NO contact function, dial range, load voltage, running current and start-up current, quantity and destination. Include the mounting drawing or existing-unit photo for a replacement.
What is the difference between KTO and KTS?
KTO is a normally closed heating contact that opens as temperature rises. KTS is a normally open cooling contact that closes as temperature rises. Choose the function before comparing the current rating.
Which documents should accompany the enquiry?
Request the model-specific dimensional and connection drawing, electrical ratings and any compliance documents required for the destination market. Identify the sample or configuration to which they must apply.
TECHNICAL ENQUIRY
Specify the control and the load.
Send the model and operating conditions below so the contact rating, housing and required documents can be checked together.
Contact CHSO →Include with your request
- KTO 013 & KTS 013 Thermostats; quantity and destination
- Thermostat: NC / NO function, temperature scale, load voltage, running current and inrush
- Heater: required wattage, mains voltage, cabinet size and minimum ambient temperature
- Available mounting space, existing-unit photo and required approval documents