Equipment-side surge protection
BY3 Surge Protective Devices
Compare BY3-2.5/150, BY3-4.0/320 and BY3-6.0/420 by maximum continuous voltage and open-circuit impulse voltage.
At a glance
Specifications & model comparison
- Maximum discharge current Imax
- 10 kA (8/20 µs)
- Nominal discharge current In
- 5 kA (8/20 µs)
- Response time
- <100 ns
- Protection degree
- IP20
- Material
- PBT
- Ambient temperature
- −40 to +80 °C
| Model | Rated voltage Un (V) | Uc (V) | Up (kV) | Open-circuit voltage Uoc, 1.2/50 µs (kV) | Enquiry |
|---|---|---|---|---|---|
| BY3-2.5/150 | 110 | 150 | ≤0.8 | 2.5 | Select for RFQ → |
| BY3-4.0/320 | 220 | 320 | ≤1.0 | 4.0 | Select for RFQ → |
| BY3-6.0/420 | 220 | 420 | ≤1.5 | 6.0 | Select for RFQ → |
Include the required pole count, electrical configuration and accessories in your enquiry. Configuration descriptions do not replace the complete ordering code.
Before ordering
Specify the configuration
- Specify the supply voltage, earthing system, pole arrangement, installation position and backup protection.
- Use the individual voltage and discharge-current ratings rather than choosing only by the largest kA value.
- The legacy B/C/D designation is not used here as proof of a current Type 1/2/3 classification; state the required tested classification and documentation in the enquiry.
- Isolate the circuit and follow the installation instructions for maintenance or replacement.
Selection questions
Practical answers for purchasing
What do the two numbers in BY3-4.0/320 describe?
The table pairs a 4.0 kV open-circuit impulse voltage Uoc with a 320 V maximum continuous operating voltage Uc. These are different voltage characteristics.
Request a quote
Build a clear enquiry.
Select a series and add the electrical details your purchasing team needs confirmed.
This tool prepares enquiry text. Copy the summary and send it through our contact page.
Contact CHSO →