Relays & Sockets
JGX Solid State Relays
Solid state relays switch an electrical load through a semiconductor output. Match the input signal, AC or DC load, operating voltage and thermal arrangement.
JGX-48 and JGX-22 configurations differ in their control input and AC or DC load circuit.
SELECTION GUIDE
Select the configuration for your application.
- 01
Control input and signal range
- 02
AC or DC load and operating voltage
- 03
Load current and thermal conditions
- 04
Mounting and heat dissipation
Technical data & product views
JGX solid state relays use different control inputs and load circuits. Select the complete suffix before specifying a relay.
| Configuration | Control input | Load circuit |
|---|---|---|
| JGX-48 DA | 3–32 V DC | 24–480 V AC |
| JGX-48 AA | 50–250 V AC | 24–480 V AC |
| JGX-48 VA | External 470 kΩ / 2 W potentiometer | 24–480 V AC |
| JGX-22 DD | 3–32 V DC | 5–220 V DC |
Specify the complete model, load type, load voltage, operating current, ambient temperature and cooling arrangement. The control-input voltage and switched-load voltage are separate specifications.
| JGX-48 DA (Basic configuration) | |||||||
|---|---|---|---|---|---|---|---|
| Load Current | 10A,15A,20A,25A,30A,40A,50A, 60A,75A,80A,90A,100A,120A | ||||||
| Load Voltage | 24-480VAC | ||||||
| Control Voltage | 3-32VDC | ||||||
| Control Current | DC3-25mA | ||||||
| On-state voltage drop | ≤1.5V | ||||||
| Off-state leakage current | ≤2mA | ||||||
| Switching time | ≤10 ms | ||||||
| Dielectric Strength | 2500VAC | ||||||
| Insulation Resistance | 1000MΩ/500VDC | ||||||
| Ambient Temperature | -30~ 75℃ | ||||||
| Mounting Methods | bolted | ||||||
| Status indicator | LED | ||||||
| Weight | 90g(10A,25A) 135g(40A ) | ||||||
| JGX-48 AA (Basic configuration) | |||||||
|---|---|---|---|---|---|---|---|
| Load Current | 10A,15A,20A,25A,30A,40A,50A, 60A,75A,80A,90A,100A,120A | ||||||
| Load Voltage | 24-480VAC | ||||||
| Control Voltage | 50-250VAC | ||||||
| Control Current | AC≤12mA | ||||||
| On-state voltage drop | ≤1.5V | ||||||
| Off-state leakage current | ≤2mA | ||||||
| Switching time | ≤10 ms | ||||||
| Dielectric Strength | 2500VAC | ||||||
| Insulation Resistance | 1000MΩ/500VDC | ||||||
| Ambient Temperature | -30~ 75℃ | ||||||
| Mounting Methods | bolted | ||||||
| Status indicator | LED | ||||||
| Weight | 90g(10A,25A) 135g(40A ) | ||||||
| JGX-48 VA ( Resistance-type on-load ) | |||||||
|---|---|---|---|---|---|---|---|
| Load Current | 10A,15A,20A,25A,30A,40A,50A, 60A,75A,80A,90A,100A,120A | ||||||
| Load Voltage | 24-480VAC | ||||||
| External control potentiometer | 470KΩ/2W | ||||||
| Control Current | / | ||||||
| On-state voltage drop | ≤1.5V | ||||||
| Off-state leakage current | ≤2mA | ||||||
| Switching time | / | ||||||
| Dielectric Strength | 2500VAC input and ouput terminal - radiator panels | ||||||
| Insulation Resistance | 1000MΩ/500VDC | ||||||
| Ambient Temperature | -30~ 75℃ | ||||||
| Mounting Methods | bolted | ||||||
| Status indicator | LED | ||||||
| Weight | 90g(10A,25A) 135g(40A ) | ||||||
| JGX-22 DD | |||||||
|---|---|---|---|---|---|---|---|
| Load Current | 10A,15A,20A,25A,30A,40A,50A, 60A,75A,80A,90A,100A,120A,150A | ||||||
| Load Voltage | 5-220VDC | ||||||
| Control Voltage | 3-32VDC | ||||||
| Control Current | DC5-25mA | ||||||
| On-state voltage drop | ≤1.5V | ||||||
| Off-state leakage current | ≤2mA | ||||||
| Switching time | ≤10 ms | ||||||
| Dielectric Strength | 2000VAC | ||||||
| Insulation Resistance | 500MΩ/500VDC | ||||||
| Ambient Temperature | -30~ 75℃ | ||||||
| Mounting Methods | bolted | ||||||
| Status indicator | LED | ||||||
| Weight | 90g(10A,25A) 135g(40A ) | ||||||
Specify your configuration.
Include the model, quantity and destination. For replacement parts, attach the existing label and installation drawing.
YOUR REQUIREMENTS
Make the inquiry specific.
Full model; control input; load voltage and current; ambient temperature; mounting and heat sink; quantity.
Saved in this browser. No message is sent.