CS-211 Caja de terminales de conmutación de 2 polos

El CS-211 era una caja de terminales de conexión con 2 polos, 11 posiciones de conexión por polo, una clasificación de 125 A/500 V y una tapa de inspección transparente.

2 poles × 11 positions125 A / 500 V100 mm length
CS-211 2-Pole Junction Terminal Box
CS-211 · Covered Junction Boxes
Datos técnicos

Especificaciones del producto

CS-211 technical specifications
ParámetroEspecificaciones
ModeloCS-211
Corriente nominal125 A
Rated voltage500 V
Poles / isolated bars2
Positions per pole11
Total connection positions22
Base materialPA66 nylon
Cover materialTransparent polycarbonate (PC)
Terminal barsBrass, 6.5 × 12 mm section
ScrewsZinc-plated steel
Base material flammabilityUL 94 V-2 (material classification)
MountingDIN rail / screw mounting
Fixing screwM4
Mounting centres80 mm
Overall L × W × H100 × 45 × 50 mm
Connections & dimensions

Pole layout & mounting dimensions

CS-211 selection table
ModeloPolacosPositions / poleTotal positionsAVL (mm)W (mm)H (mm)Fixing centres (mm)
CS-21121122125500100455080

Positions on the same bar are electrically common. A material flammability class is not a product approval. Dimensions are in millimetres.

Aplicación y instalación

Select for the complete panel

Use the 2-pole layout where 2 separate potentials must remain isolated, with up to 11 connection positions on each bar. Allow space above the cover for screw access and beside the box for cable bending.

Compatibilidad de la aplicación

  • Distribution and control panels
  • Separated phase and neutral termination arrangements
  • Accessible multi-branch wiring within enclosed equipment

Secuencia de instalación

  1. Isolate the circuit and verify that it is de-energised.
  2. Secure the terminal assembly to the matching rail or mounting surface. Keep accessible metal parts separated from other potentials.
  3. Prepare conductors for full engagement in the clamp, without damaged strands or exposed copper outside the entry.
  4. Use the clamping screw appropriate to the entry; support wires so that cable tension is not carried by the terminal.
  5. Check conductor retention, circuit identification and continuity. Close any fitted cover before energising the completed assembly.
Respondes de forma práctica

Preguntas frecuentes

How many circuits does CS-211 provide?

The box contains 2 separate terminal bars. Each bar has 11 common-potential positions; the box has 22 positions in total.

Is 125 A multiplied by the number of terminals?

No. The number of terminal positions does not multiply the current rating. Coordinate the feeder, branch conductors and circuit protection for the actual load.

Is this a weatherproof junction enclosure?

This is a covered terminal assembly for installation inside an electrical enclosure. The transparent cover provides access control and visibility; it is not a weatherproof enclosure rating.

Does UL 94 V-2 mean the complete product is UL certified?

No. UL 94 V-2 describes the specified base material’s flammability classification, not certification of the complete terminal box.

Consultas sobre distribuidores y OEM

Especifica la conexión.
Construya una investigación clara.

Include CS-211 2-Pole Junction Terminal Box model code, quantities, conductor sizes, destination and packaging requirements.

Solicite un presupuesto
WhatsApp